Voltage Drop Calculator

Calculate voltage drop over a conductor run and check it against the recommended limit.

Your numbers

Result

Voltage drop 6.0 Volts
Drop as a percentage 2.49%
Voltage at the load 234.0
Against the 3% guideline Within the 3% guideline
Drop is 6.0 V (2.49%), leaving 234.0 V at the load, within the 3% guideline.

Electrical work is life-safety work governed by the NEC or your local code, and must be designed and installed by a licensed electrician. Conductor and overcurrent sizing depends on ambient temperature, conductor bundling, termination ratings, continuous-load rules and more. This is an educational estimate and must never be used as the basis for an installation. The 3% branch-circuit and 5% total guideline is an NEC recommendation in informational notes, not a hard requirement, but exceeding it causes dim lights, poor motor starting and wasted energy.

Get a Free Business Audit

Questions

About this calculator

How much voltage drop is acceptable?

The commonly used guideline is 3% on a branch circuit and 5% total from service to load. It is advisory in the NEC rather than mandatory, but it is good practice.

Why does a long run need bigger wire?

Resistance rises with length, so drop rises proportionally. On long runs the conductor is sized by voltage drop rather than by ampacity, often two or three sizes above what the current alone would need.

The formula

single phase: VD = 2 × K × I × L ÷ circular mils (K = 12.9 copper, 21.2 aluminium)