bdevy.

Electrical

Voltage Drop Calculator

Compare conductor voltage loss across single-phase and three-phase runs using the actual route length and expected load.

Your numbers

Result

Voltage drop 6.0 Volts
Drop as a percentage 2.49%
Voltage at the load 234.0
Against the 3% guideline Within the 3% guideline
Drop is 6.0 V (2.49%), leaving 234.0 V at the load, within the 3% guideline.

Electrical work is life-safety work governed by the NEC or your local code, and must be designed and installed by a licensed electrician. Conductor and overcurrent sizing depends on ambient temperature, conductor bundling, termination ratings, continuous-load rules and more. This is an educational estimate and must never be used as the basis for an installation. The 3% branch-circuit and 5% total guideline is an NEC recommendation in informational notes, not a hard requirement, but exceeding it causes dim lights, poor motor starting and wasted energy.

Get a Free Business Audit

What moves the number

  • One-way distance includes the installed route, not just the floor-plan separation.
  • Conductor area and material affect resistance.
  • The selected phase model changes the drop calculation.

Where this one goes wrong

A steady running-current estimate may miss a short starting dip. This tool also does not model every upstream loss, connection condition or AC impedance effect. A passing percentage alone does not prove satisfactory equipment operation.

Questions

About this calculator

Should I double the cable distance?

Enter the one-way run requested by the form. The calculation applies its own circuit factor, so doubling the entry would count the return path again.

Does the percentage include the feeder?

Only the run entered here is represented. Assess the complete supply path separately when a branch begins at a distant distribution board.

Is the displayed guideline a compliance verdict?

No. Voltage-drop design is a planning check against local code, project specifications and equipment requirements; ampacity and protection require their own verification.

How useful was this calculator?

Not rated yet. Yours would be the first.

The formula

single phase: VD = 2 × K × I × L ÷ circular mils (K = 12.9 copper, 21.2 aluminium)

Put this calculator on your site

Free to embed. Paste this where you want it to appear. It stays up to date automatically because it loads from BDEVY.

Please keep the attribution line. It is the only thing we ask in return.

How to use this calculator

  1. Conductor size (AWG). Enter your own figure; the page starts at 10 AWG.
  2. Conductor material. Enter your own figure; the page starts at Copper.
  3. Load current (A). Enter your own figure; the page starts at 20.
  4. One-way run length (ft). Enter your own figure; the page starts at 120.
  5. System voltage (V). Enter your own figure; the page starts at 240.
  6. Phase. Enter your own figure; the page starts at Single phase.

The result updates as you type, so you can try a figure, see what it does to voltage drop, and change it back. Nothing you enter is sent anywhere or saved.

A worked example

These are the figures the calculator opens with. Every number in the results column below is produced by the same calculation the page runs, so you can follow it through before putting your own figures in.

What goes in

InputValue
Conductor size (AWG)10 AWG
Conductor materialCopper
Load current (A)20
One-way run length (ft)120
System voltage (V)240
PhaseSingle phase

What comes out

ResultValue
Voltage drop main result6.0
Drop as a percentage2.49%
Voltage at the load234.0
Against the 3% guidelineWithin the 3% guideline

Drop is 6.0 V (2.49%), leaving 234.0 V at the load, within the 3% guideline.

How sensitive the answer is

Holding everything else steady and changing only load current (a), this is what happens to voltage drop. It is worth knowing which of your inputs the answer actually hinges on, and which barely move it.

Load current (A)Voltage drop
10 3.0
15 4.5
20 example above 6.0
30 8.9
40 11.9

Every other input is held at the example value while this one changes, which is not how a real job behaves. Treat it as a guide to which number matters most, not as five separate quotes.

What each figure means

Conductor size (AWG)
Choose from 14 AWG, 12 AWG, 10 AWG, 8 AWG, 6 AWG, 4 AWG, 3 AWG, 2 AWG, 1 AWG, 1/0 AWG, 2/0 AWG, 3/0 AWG, 4/0 AWG.
Conductor material
Choose from Copper, Aluminium.
Load current (A)
A number, between 0 and 5000, starting at 20.
One-way run length (ft)
A number, between 0 and 20000, starting at 120.
System voltage (V)
A number, between 0 and 100000, starting at 240.
Phase
Choose from Single phase, Three phase.

What the results tell you

ResultWhat it is
Voltage dropThe headline result. A decimal figure.
Drop as a percentageA percentage.
Voltage at the loadA decimal figure.
Against the 3% guidelineA category or planning selection, rather than a measured quantity.

Before you rely on this number

Conductor sizing, voltage drop and load figures are governed by code, and the code takes precedence over any calculator. Ambient temperature, conduit fill, continuous load factors and the specific installation all change the answer. Treat this as a first pass, not a design.