Solar Battery Size Calculator

Sizes a battery, where usable capacity and nameplate capacity are different.

Your numbers

How long it must last with no sun at all.
$

Result

Nameplate capacity needed 17.5 kWh
Usable energy that gives 12.6 kWh
Delivered after losses 12.0 kWh
Installed cost $15,789
Rated cycle life 6,000 Cycles
To deliver 12.0 kWh you need a 17.5 kWh nameplate bank. Depth of discharge and round-trip losses mean only 12.0 kWh of it ever reaches the load.

Depth of discharge is how much of the nameplate you may actually use. Lithium iron phosphate tolerates 80% to 90%; lead acid should not go past 50% if you want it to last. Round-trip efficiency then takes another 5% to 15% on the way in and out. Cycle life figures are manufacturer ratings at favourable temperature and discharge rate; heat and deep fast cycling both shorten them considerably.

Get a Free Business Audit

How the calculation works

The energy to be supported divided by usable capacity, where usable is the nameplate capacity multiplied by the permitted depth of discharge and adjusted for round-trip efficiency and inverter conversion. Chemistry sets the depth of discharge, and the difference between chemistries is large enough to change the battery count.

What moves the number

  • Energy to be supported and for how long.
  • Chemistry, which sets permitted depth of discharge.
  • Round-trip and inverter efficiency.
  • Temperature, which affects available capacity.

Where this one goes wrong

Sizing from nameplate capacity rather than usable capacity undersizes the battery by the whole depth of discharge margin, and lithium iron phosphate and lead acid differ enough here that a swap between them is not a like-for-like substitution. Efficiency losses apply on the way in and the way out, so the energy drawn from the battery is less than the energy stored in it. Cold also reduces available capacity, which matters where the battery is in an unheated space.

Before you quote

  • Size from usable capacity, not nameplate.
  • Use the chemistry's actual depth of discharge limit.
  • Allow for round-trip and inverter losses.

Questions

About this calculator

Why can I not use a battery's full capacity?

Because depth of discharge is limited by chemistry, and discharging beyond it shortens life sharply or is prevented by the management system. Lithium iron phosphate permits far deeper discharge than lead acid, which makes them very different in usable terms.

Do efficiency losses matter?

Yes, on both sides: energy is lost charging and lost again converting on discharge. The energy actually delivered to a load is meaningfully less than the energy sent to the battery, and sizing that ignores it falls short in practice.

Does cold affect battery capacity?

Substantially, which matters where a battery sits in an unheated garage or outdoors. Available capacity falls as temperature drops, and some chemistries also restrict charging below a threshold, so the installed location is part of the sizing.

How useful was this calculator?

Not rated yet. Yours would be the first.

The formula

nameplate = energy needed / (depth of discharge x (1 - reserve) x round-trip efficiency)

Put this calculator on your site

Free to embed. Paste this where you want it to appear. It stays up to date automatically because it loads from BDEVY.

Please keep the attribution line. It is the only thing we ask in return.

How to use this calculator

  1. Energy to cover (kWh). Enter your own figure; the page starts at 12.
  2. Days of autonomy. How long it must last with no sun at all.
  3. Battery type. Enter your own figure; the page starts at Lithium iron phosphate (80% usable, 95% efficient).
  4. Reserve you will not touch (%). Enter your own figure; the page starts at 10.
  5. Installed cost per kWh ($). Enter your own figure; the page starts at $900.

The result updates as you type, so you can try a figure, see what it does to nameplate capacity needed, and change it back. Nothing you enter is sent anywhere or saved.

A worked example

These are the figures the calculator opens with. Every number in the results column below is produced by the same calculation the page runs, so you can follow it through before putting your own figures in.

What goes in

InputValue
Energy to cover (kWh)12
Days of autonomy1
Battery typeLithium iron phosphate (80% usable, 95% efficient)
Reserve you will not touch (%)10
Installed cost per kWh$900

What comes out

ResultValue
Nameplate capacity needed main result17.5
Usable energy that gives12.6
Delivered after losses12.0
Installed cost$15,789
Rated cycle life6,000

To deliver 12.0 kWh you need a 17.5 kWh nameplate bank. Depth of discharge and round-trip losses mean only 12.0 kWh of it ever reaches the load.

How sensitive the answer is

Holding everything else steady and changing only installed cost per kwh, this is what happens to nameplate capacity needed. It is worth knowing which of your inputs the answer actually hinges on, and which barely move it.

Installed cost per kWh ($)Nameplate capacity needed
$450 17.5
$675 17.5
$900 example above 17.5
$1,350 17.5
$1,800 17.5

Every other input is held at the example value while this one changes, which is not how a real job behaves. Treat it as a guide to which number matters most, not as five separate quotes.

What each figure means

Energy to cover (kWh)
A number, between 0 and 5000, starting at 12.
Days of autonomy
How long it must last with no sun at all.
Battery type
Choose from Lithium iron phosphate (80% usable, 95% efficient), Lithium NMC (90% usable, 94% efficient), AGM lead acid (50% usable, 85% efficient), Flooded lead acid (50% usable, 80% efficient).
Reserve you will not touch (%)
A number, between 0 and 50, starting at 10.
Installed cost per kWh ($)
A money amount, starting at $900.

What the results tell you

ResultWhat it is
Nameplate capacity neededThe headline result. A decimal figure.
Usable energy that givesA decimal figure.
Delivered after lossesA decimal figure.
Installed costA money figure.
Rated cycle lifeA number.

A design still needs a site visit

Output and sizing figures use the assumptions you enter, not measured irradiance, shading or roof orientation at your address. Real production depends on all three, plus inverter behaviour and local interconnection rules.

Estimating is the easy part

The jobs you never hear about cost more than the ones you mis-measure. BDEVY builds the marketing, systems and automation that bring them in.