bdevy.

Solar & battery

Solar Array Calculator

Configures an array, where string design is constrained at both voltage limits.

Your numbers

F

Result

Array power 9,600 Watts DC
String voltage at max power 414.0 Volts
Open circuit voltage when cold 549.6 Volts, the inverter limit check
Array current 23.2 Amps
Total panels 24
9,600 watts from 24 panels. Strings run at 414.0 V in operation, but reach 549.6 V open circuit at 10 F. That cold figure is the one that must stay under the inverter's maximum.

The cold open-circuit voltage is the number that damages inverters, and it is checked against the record low for the site rather than a typical winter morning. Exceeding the inverter maximum can destroy it and is not covered by warranty. Panel datasheets give an exact temperature coefficient; the 0.3% figure here is a common approximation for crystalline silicon.

Get a Free Business Audit

How the calculation works

Modules arranged into strings, with the string voltage checked against the inverter's maximum input at the coldest expected temperature and against its minimum operating voltage at the hottest. Both limits bind: too long a string exceeds the maximum in cold weather, too short a string drops below the minimum in heat.

What moves the number

  • Module open circuit and maximum power voltages.
  • Coldest and hottest expected cell temperatures at the site.
  • Inverter maximum input and operating voltage window.
  • Number of strings the inverter accepts.

Where this one goes wrong

Designing to only one of the two limits is the usual error, and the consequences differ: exceeding the maximum input voltage can damage the inverter, while dropping below the operating minimum simply stops production on the hottest afternoons when it was most wanted. Check both using the site's temperature extremes. The code and the adopted edition also govern the calculation method, so the design should be done to the text the inspector will apply.

Before you quote

  • Check string voltage at both temperature extremes.
  • Use site-specific record temperatures, not regional averages.
  • Design to the code edition the local authority has adopted.

Where the rules come from

Questions

About this calculator

What limits how many modules go in a string?

Two limits. The inverter's maximum input voltage, checked at the coldest expected temperature, and its minimum operating voltage, checked at the hottest. Designing to only one is the usual error and both have real consequences.

What happens if a string is too short?

It can drop below the inverter's operating voltage on the hottest afternoons, stopping production exactly when it was most valuable. That failure is less dramatic than exceeding the maximum and it quietly costs energy every summer.

Which temperatures should be used?

Site-specific records rather than regional averages, because the extremes are what bind. Published temperature data for the location is available and using an average instead is how strings end up outside the window on the few days it matters.

How useful was this calculator?

Not rated yet. Yours would be the first.

The formula

string voltage = panels in series x Vmp; cold Voc adds roughly 0.3% per degree C below 25

Put this calculator on your site

Free to embed. Paste this where you want it to appear. It stays up to date automatically because it loads from BDEVY.

Please keep the attribution line. It is the only thing we ask in return.

How to use this calculator

  1. Panel rating (watts). Enter your own figure; the page starts at 400.
  2. Panel voltage at max power (Vmp). Enter your own figure; the page starts at 34.5.
  3. Open circuit voltage (Voc). Enter your own figure; the page starts at 41.2.
  4. Panel current at max power (Imp). Enter your own figure; the page starts at 11.6.
  5. Panels in series per string. Enter your own figure; the page starts at 12.
  6. Parallel strings. Enter your own figure; the page starts at 2.

The result updates as you type, so you can try a figure, see what it does to array power, and change it back. Nothing you enter is sent anywhere or saved.

A worked example

These are the figures the calculator opens with. Every number in the results column below is produced by the same calculation the page runs, so you can follow it through before putting your own figures in.

What goes in

InputValue
Panel rating (watts)400
Panel voltage at max power (Vmp)34.5
Open circuit voltage (Voc)41.2
Panel current at max power (Imp)11.6
Panels in series per string12
Parallel strings2
Coldest expected temperature (F)10 F

What comes out

ResultValue
Array power main result9,600
String voltage at max power414.0
Open circuit voltage when cold549.6
Array current23.2
Total panels24

9,600 watts from 24 panels. Strings run at 414.0 V in operation, but reach 549.6 V open circuit at 10 F. That cold figure is the one that must stay under the inverter's maximum.

How sensitive the answer is

Holding everything else steady and changing only panel rating (watts), this is what happens to array power. It is worth knowing which of your inputs the answer actually hinges on, and which barely move it.

Panel rating (watts)Array power
200 4,800
300 7,200
400 example above 9,600
600 14,400
800 19,200

Every other input is held at the example value while this one changes, which is not how a real job behaves. Treat it as a guide to which number matters most, not as five separate quotes.

What each figure means

Panel rating (watts)
A number, between 0 and 1000, starting at 400.
Panel voltage at max power (Vmp)
A number, between 0 and 200, starting at 34.5.
Open circuit voltage (Voc)
A number, between 0 and 250, starting at 41.2.
Panel current at max power (Imp)
A number, between 0 and 40, starting at 11.6.
Panels in series per string
A number, between 0 and 40, starting at 12.
Parallel strings
A number, between 0 and 60, starting at 2.
Coldest expected temperature (F) (F)
Measured in F, between -60 and 90, starting at 10 F.

What the results tell you

ResultWhat it is
Array powerThe headline result. A number.
String voltage at max powerA decimal figure.
Open circuit voltage when coldA decimal figure.
Array currentA decimal figure.
Total panelsA number.

A design still needs a site visit

Output and sizing figures use the assumptions you enter, not measured irradiance, shading or roof orientation at your address. Real production depends on all three, plus inverter behaviour and local interconnection rules.