Solar Cable Size Calculator

Sizes cable, where voltage drop usually governs rather than ampacity.

Your numbers

%
DC runs are held tighter than AC, usually 2% or less.

Result

Cable size 6 AWG
Circular mils needed 20,156
Drop at that size 1.54%
Volts lost 0.7
6 AWG keeps the drop to 1.54% over 25 feet, losing 0.7 volts.

DC circuits are held to a tighter drop than AC because the voltage is lower, so the same lost volts are a much larger share. This sizes on voltage drop only; the cable must independently satisfy ampacity, conduit fill, temperature derating and any code requirement for the specific conductor type. Solar DC circuits also have their own NEC article with additional rules.

Get a Free Business Audit

How the calculation works

Two separate requirements: ampacity sufficient for the current with the code's safety factors and any derating for temperature and bundling, and a conductor large enough to keep voltage drop within an acceptable percentage over the run length. The larger of the two governs, and on long low-voltage runs that is almost always voltage drop.

What moves the number

  • Current, with code safety factors applied.
  • One-way run length, which doubles in the drop calculation.
  • System voltage, since drop matters proportionally more at low voltage.
  • Ambient temperature and conduit fill, which derate ampacity.

Where this one goes wrong

Voltage drop is proportional to current and length and inversely proportional to voltage, which is why a low-voltage DC run of any distance needs conductors far larger than ampacity alone would suggest, and why raising system voltage is often cheaper than upsizing cable. Code minimum ampacity does not address drop at all. Conductor sizing for PV also involves specific code multipliers and derating rules, and the adopted edition and the inspector govern rather than a remembered figure.

Before you quote

  • Size for voltage drop as well as ampacity, and take the larger.
  • Use the one-way length doubled in the drop calculation.
  • Apply temperature and conduit derating from the adopted code.

Where the rules come from

Questions

About this calculator

Why is my cable bigger than the ampacity table says?

Because voltage drop usually governs on anything but a short run. Drop is proportional to current and length and inversely proportional to voltage, so a low-voltage DC run needs far larger conductors than ampacity alone would require.

Is it cheaper to raise system voltage or upsize cable?

Frequently raising the voltage, since drop falls proportionally while conductor cost rises steeply with size. That is why larger off-grid systems use 48 volt banks rather than 12, and why long array runs are configured at high voltage.

Which code rules apply to PV conductors?

Article 690 of NFPA 70 plus the general conductor rules, with specific multipliers for continuous current and derating for temperature and conduit fill. The edition adopted locally and the inspector govern, so the current adopted text is the authority.

How useful was this calculator?

Not rated yet. Yours would be the first.

The formula

circular mils = 2 x K x amps x distance / allowable volts dropped

Put this calculator on your site

Free to embed. Paste this where you want it to appear. It stays up to date automatically because it loads from BDEVY.

Please keep the attribution line. It is the only thing we ask in return.

How to use this calculator

  1. Current (A). Enter your own figure; the page starts at 30.
  2. System voltage. Enter your own figure; the page starts at 48.
  3. One-way run (ft). Enter your own figure; the page starts at 25.
  4. Acceptable voltage drop (%). DC runs are held tighter than AC, usually 2% or less.
  5. Conductor. Enter your own figure; the page starts at Copper.

The result updates as you type, so you can try a figure, see what it does to cable size, and change it back. Nothing you enter is sent anywhere or saved.

A worked example

These are the figures the calculator opens with. Every number in the results column below is produced by the same calculation the page runs, so you can follow it through before putting your own figures in.

What goes in

InputValue
Current (A)30
System voltage48
One-way run (ft)25
Acceptable voltage drop2%
ConductorCopper

What comes out

ResultValue
Cable size main result6
Circular mils needed20,156
Drop at that size1.54%
Volts lost0.7

6 AWG keeps the drop to 1.54% over 25 feet, losing 0.7 volts.

How sensitive the answer is

Holding everything else steady and changing only current (a), this is what happens to cable size. It is worth knowing which of your inputs the answer actually hinges on, and which barely move it.

Current (A)Cable size
15 10
22.5 8
30 example above 6
45 4
60 4

Every other input is held at the example value while this one changes, which is not how a real job behaves. Treat it as a guide to which number matters most, not as five separate quotes.

What each figure means

Current (A)
A number, between 0 and 2000, starting at 30.
System voltage
A number, between 0 and 1500, starting at 48.
One-way run (ft)
A number, between 0 and 2000, starting at 25.
Acceptable voltage drop (%)
DC runs are held tighter than AC, usually 2% or less.
Conductor
Choose from Copper, Aluminium.

What the results tell you

ResultWhat it is
Cable sizeThe headline result. A category or planning selection, rather than a measured quantity.
Circular mils neededA number.
Drop at that sizeA percentage.
Volts lostA decimal figure.

A design still needs a site visit

Output and sizing figures use the assumptions you enter, not measured irradiance, shading or roof orientation at your address. Real production depends on all three, plus inverter behaviour and local interconnection rules.

Estimating is the easy part

The jobs you never hear about cost more than the ones you mis-measure. BDEVY builds the marketing, systems and automation that bring them in.