bdevy.

Electrical

Electrical Wire Size Calculator

Review a preliminary conductor gauge alongside the gauge indicated by this tool's fixed voltage-drop comparison.

Your numbers

Result

Wire size 10 AWG
Amps the wire must carry 30
Voltage drop at that size 1.86%
Size after voltage drop 10
For 30 amps you need 10 AWG. Over 60 feet that drops 1.86%, so on voltage drop alone you would run 10 AWG.

A planning estimate, not a code calculation. Conductor sizing, overcurrent protection and load calculations are governed by the NEC as adopted and amended where you are, and by the listing of the equipment involved. Have the design confirmed by a licensed electrician and inspected. Ampacities here are the 75 degree copper and aluminium columns, before any derating for ambient temperature or for more than three current-carrying conductors in a raceway.

Get a Free Business Audit

What moves the number

  • The load is adjusted by the selected duration assumption.
  • Copper and aluminium use different lookup values.
  • The one-way route and system voltage determine the separate drop result.

Where this one goes wrong

The displayed Wire size is the table-based selection, while Size after voltage drop is a separate output. Do not read the first as a complete recommendation. Neither incorporates every installation adjustment or checks all possible protection arrangements.

Questions

About this calculator

Why are two gauges displayed?

One starts with the simplified current table. The other explores the run-length constraint, which can require a larger conductor even where the first gauge carries the current on paper.

Does the voltage selector change the circuit model?

It changes the voltage used in the percentage calculation. Selecting a commercial voltage does not turn the fixed circuit formula into a complete three-phase design.

What remains before specifying a conductor?

Verify terminations, cable type, derating and protection under the applicable code and equipment data. This is a planning check, not a substitute for that design.

How useful was this calculator?

Not rated yet. Yours would be the first.

The formula

design amps = load x 1.25 if continuous; voltage drop = 2 x K x amps x distance / circular mils

Put this calculator on your site

Free to embed. Paste this where you want it to appear. It stays up to date automatically because it loads from BDEVY.

Please keep the attribution line. It is the only thing we ask in return.

How to use this calculator

  1. Load (amps). Enter your own figure; the page starts at 30.
  2. Conductor. Enter your own figure; the page starts at Copper.
  3. Load type. Enter your own figure; the page starts at Normal load.
  4. One-way run length (ft). Enter your own figure; the page starts at 60.
  5. Voltage. Enter your own figure; the page starts at 240 V.

The result updates as you type, so you can try a figure, see what it does to wire size, and change it back. Nothing you enter is sent anywhere or saved.

A worked example

These are the figures the calculator opens with. Every number in the results column below is produced by the same calculation the page runs, so you can follow it through before putting your own figures in.

What goes in

InputValue
Load (amps)30
ConductorCopper
Load typeNormal load
One-way run length (ft)60
Voltage240 V

What comes out

ResultValue
Wire size main result10
Amps the wire must carry30
Voltage drop at that size1.86%
Size after voltage drop10

For 30 amps you need 10 AWG. Over 60 feet that drops 1.86%, so on voltage drop alone you would run 10 AWG.

How sensitive the answer is

Holding everything else steady and changing only load (amps), this is what happens to wire size. It is worth knowing which of your inputs the answer actually hinges on, and which barely move it.

Load (amps)Wire size
15 14
23 10
30 example above 10
45 8
60 6

Every other input is held at the example value while this one changes, which is not how a real job behaves. Treat it as a guide to which number matters most, not as five separate quotes.

What each figure means

Load (amps)
A number, between 0 and 400, starting at 30.
Conductor
Choose from Copper, Aluminium.
Load type
Choose from Normal load, Continuous, 3 hours or more.
One-way run length (ft)
A number, between 0 and 2000, starting at 60.
Voltage
Choose from 120 V, 240 V, 208 V, 480 V.

What the results tell you

ResultWhat it is
Wire sizeThe headline result. A category or planning selection, rather than a measured quantity.
Amps the wire must carryA number.
Voltage drop at that sizeA percentage.
Size after voltage dropA category or planning selection, rather than a measured quantity.

Before you rely on this number

Conductor sizing, voltage drop and load figures are governed by code, and the code takes precedence over any calculator. Ambient temperature, conduit fill, continuous load factors and the specific installation all change the answer. Treat this as a first pass, not a design.

Estimating is the easy part

The jobs you never hear about cost more than the ones you mis-measure. BDEVY builds the marketing, systems and automation that bring them in.